60203005 Front
60203005 Front Open
ac-powercube-remote-panel-drawing
60203005 Front
60203005 Front Open
ac-powercube-remote-panel-drawing

AC PowerCube 24 VDC – 14000 VA

Experience the reliability of the AC PowerCube 24 VDC – 14000 VA, a robust 24 VDC sine wave inverter built to the highest industrial specifications. This unit effectively converts power from a 24 VDC battery to provide a substantial 14 kVA output at 230 VAC, configurable for 50 or 60 Hz operation.

This innovative sine wave inverter processes battery power to deliver high-quality 230 VAC power.

  • State-of-the-art high-frequency switching mode technology
  • Construction adhering to stringent industrial quality
  • Reliable high output with excellent peak power
  • Efficient, lightweight 14 kVA design
  • Over 92% efficiency rate with reduced power loss
  • Quadruple DC connectors 4x positive, 4x negative
  • Can be connected to 4 battery banks
  • Whisper-quiet with no electronic interference
  • Temperature-regulated cooling fans, ideal for warm climates
  • Compatible with the WhisperPower DC PowerCube framework
pure sine wave inverter ac powercube in vehicle

High-Performance Sine Wave Inverter

The durable AC PowerCube 24 VDC – 14000 VA, enclosed in a solid aluminum frame, is designed to perform reliably even in adverse conditions, with a conformal coating protecting against environmental damages.

Technological Excellence

Featuring high-frequency switching technology, the AC PowerCube 24 VDC – 14000 VA offers advantages over older transformer-based models by being quieter, more compact, and efficient. It delivers stable, high-quality AC power consistently.

pure sine wave inverter ac powercube in system
pure sine wave inverter ac powercube 14000

Advanced Integration and Control

Outfitted with analog controls and available digital enhancements, the PowerCube offers comprehensive control options. It features WhisperConnect for seamless connectivity, USB for easy updates, and laptop compatibility for adjustments.

The AC PowerCube 24 VDC – 14000 VA integrates flawlessly into WhisperPower systems, providing advanced energy management solutions for any setting.

Product specifications

ARTICLE NUMBER
60203005AC PowerCube 24 VDC – 14000 VA
GENERAL
Nominal output voltage230 V (±5%), Phase, Neutral, Earth *)
Nominal output frequency (adjustable to 60 HZ)50 Hz (± 0,01 Hz)
Length x width x height, mm (in.)620 × 316 × 575 (24.4 x 12.4 x 22.6)
Weight kg (lb.)40 (88.2)
Nominal battery voltage24 VDC
Nominal power P30 (cos phi = 1) (30 min at 40°C)14000 W
Peak power (20 s)28000 W
Continuous power (cos phi = 1) (40°C)12000 W
AC connection (output)Internal terminal block, screw terminal (4 .. 6 mm2)
DC connection4 × M10 (2 per battery bank)
Minimum capacity of battery bank800 Ah
Efficiency> 85%
Peak efficiency> 92%
Noise level (at 1 m)< 48 dBA
OperationPower switch (on / off / remote), the DC inputs (on / off), Remote panel switch (On / Off) *
IndicatorsAC present, DC 1 present, DC (1) load, DC 2 present, DC (2) load, AC current, AC voltage
SafetyShort circuit, overload, overheating, battery voltage too low / high
TECHNICAL SPECIFICATIONS
TechnologySix-step multiphase flyback, Switched mode technology
Low battery switch off19 V (±0.5 V)
Low battery switch on22 V (±0.5 V)
High battery switch off32 V (±0.5 V)
High battery switch on30 V (±0.5 V)
Maximum ripple on DC (battery)5% RMS
Input current (nominal load)4 x 200 A
Consumption (no load)<2 x 550 mA, 24 W
Total harmonic distortion (THD)< 5% (normal)
Allowable power factor0 <cos phi <1
CONDITIONS
Ambient operating temperature-20°C .. 40°C
Storage temperature-25°C .. 80°C (derating above 40 °C)
Relative humidityMax 95%, non-condensing
International Protection ratingIP23
CoolingNatural / forced
CONFORMITY
EU DirectiveEMC Directive 2004/108 / EC, EMC 2004/104 / EC (automotive), Low Voltage Directive 2006/95 / EC
StandardsEN 55022 (emission) EN 61000-3-2 (harmonic distortion), EN 61000-4-11, EN 61000-3-3 (voltage variations), EN 61000-6-2 A (immunity) and EN 60950-1 (safety ) AND 68-2-6 (vibration), EN 60945 (navigation and radio communications), UL 458